Novel dynamic modeling of a microchannel-based thermosyphon is presented/validated.
A geometry is proposed/simulated for the retrofitting of a commercial 2U-server.
Both stable and unstable solutions are found for the steady-state.
A riser diameter increase of 30% led up to 60% increase in flow rate.
The flow self-redistributes into the highest heat load CPU during parallel cooling.