Field measurements of supermarket refrigeration systems. Part II: Analysis of HFC refrigeration systems and comparison to CO2 trans-critical
详细信息    查看全文
文摘
Three Swedish supermarkets using typical HFC refrigeration solutions are analyzed. Field measurements of the HFC systems are compared to CO2 trans-critical systems. Detailed analysis of field measurements combined with modelling is performed. CO2 systems have higher COP than HFC systems for outdoor temperatures below 24 °C. CO2 systems use about 20% less energy than a typical HFC system.