开展110kV交流架空输电线路电磁环境影响理论计算与测试分析。结果表明:理论计算结果与监测结果基本吻合,其分布规律和变化趋势基本一致,其中理论计算结果更为保守。输变电项目环境影响评价中,采用理论计算结果来反映输电线路电磁环境影响是合理有效的。
The electromagnetic environmental impact of 110 kV AC overhead transmission lines was calculated and measured. The result of theoretically calculation basically tallied with measurement, and their distribution regulation and variation trend were nearly the same. The result of theoretically calculation was more conservative. Took the result of theoretically calculation to reflect the electromagnetic environmental impact of transmission lines was reasonability and effective in environmental impact assessment of power transmission and transformation projects.